Primary reserve
The primary reserve is the capacity that is activated by the primary control system.
The primary control system is an automated device (installed locally on production equipment with a capacity of 5 MW or more), which ensures a constant ratio between frequency changes and production (capacity) changes in no more than 30 seconds.
Context
- The requirements for the primary reserve and the delivery of the primary control contribution have been laid down in the System Code.
- The settings of the primary control systems on the production equipment are based on the values laid down in the document on UCTE agreements.
- In accordance with UCTE policies, TSOs are held responsible within the UCTE for the quality of the primary control contributions after disruptions www.ucte.org. Each TSO analyses and reports on the quality of its own primary response after a European disruption of over 1000 MW.
Compensation for primary reserve
The maintenance of the primary reserve and the provision of the primary control contribution are not compensated for.
Explanation
The purpose of the primary reserve is to stabilize frequency disruptions in the entire (internationally) interconnected high-voltage grid, regardless of the cause and location of these disruptions. Serious frequency disruptions can result in automatic load shedding and in the worst case initiate a black-out.
The minimum size required for primary contributions is determined annually at ENTSO-E Region Continental Europe (formerly UCTE) level and is in proportion to the total production volume in the areas controlled by the TSOs. For 2011 the frequency bias for the Netherlands has been set at 1106 MW/Hz. This value equals 4,2% of the frequency bias for the entire synchronously interconnected European grid.
The above means that in the event of an outage of 1000 MW somewhere in continental Europe, a contribution of approximately 42 MW is expected from the Netherlands. The maximum possible outage is deemed to be 3000 MW. Taking the percentage of 4,2% into account, this means that the Netherlands must have an available primary reservecapacity of 125 MW in both regulating directions.
| Year | Share in UCTE production (%) | Minimum primary reserve (MW) |
|---|---|---|
2010 2011 | 3,9 4,2 | 116 125 |
These Dutch data for 2010 and 2011were calculated proportionally on the basis of the total known Dutch electrical energy production (sources: Statistics Netherlands and TenneT) in 2008 and 2009 respectively.



